18 / 76 BKI16ATEX0018X htk4014a0600p_03
Nozzles penetrating into tank
Caution: Do not use nozzles that penetrate into the tank.
This will disturb the emitted pulse.
Installation of two devices
If two devices are to be used on the same tank, these should be
mounted at a distance of at least 2 m or 6.5 ft away from each other.
If not, interferences from the electromagnetic (EM) fields generated
by both instruments may cause measurement errors.
Coaxial probes: the outer shell of the probe contains the EM field: no
minimum distance required.