EasyManua.ls Logo

NMFIRE NFPA20 - 3.9 Fire Pump Controller Pressure Sensing Line

Default Icon
62 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
30
3.9 Fire Pump Controller Pressure Sensing Line
1. For all fire pumps, including jockey pumps, each controller shall have its own separate
pressure sensing line;
2. Pressure sensing pipe must be made of hard brass or not less than 300 stainless steel,
pipe diameter is 1/2" (15mm).
3. Install two check valves in the pressure sensing line, the installation distance of check
valve must be 1.5m, and drill a 2.4mm (3/32") through hole on the disc of check valve.
Pay attention to the installation direction of these two check valves.
4. Install two inspection test valves in the pressure sensing line;see figure 1 and figure 2
5. The pressure sensing pipeline of each fire pump is connected between "check valve" and
"globe valve" at the outlet of the pump.
Notes:
1. Solenoid drain valve used for engine-driven fire pumps can be at A,B,or inside controller
enclosure.
2. If water is clean,ground-face unions with noncorrosive diaphragms driled for 3/32
in.orifices can be used in place of the check valves.
FIGURE A.3.9APressure Sensing Line
FIGURE 1
FIGURE 2

Table of Contents