4.1.1 Jockey Pump Start Requirements
1. Check and confirm that
there is no foreign body in
the suction pipe and the
water supply of the suction
pipe is normal. Close the
outlet valve of the pump
and open the valve of the
suction pipe for water
supply.
2. Remove the plug from the
top of the pump and slowly
fill the pump with liquid.
Reinstall the plug and
tighten it.
(Note: for high level water
source tank, remove the
wire plug at the top of the
pump, no need to inject
liquid, after the gas in the
pump is completely
discharged, reinstall the wire
plug and tighten it.)
3. From the motor fan cover
end, observe whether the
pump rotation direction is
correct.