7. When there is a steady
outflow of liquid from the
exhaust valve, close the
exhaust valve. At this time,
open the outlet valve fully.
8. For more details, please
refer to the vertical
multi-stage pump manual.
4.1.2 Pressure Tank (if install)
Note: if there is no pressure tank in the fire pump package system, please ignore this part. If
there is a pressure tank, please use it as required.
1. The pre-charging pressure of the pressure tank has been set before delivery, and the
pressure is 4bar. If the user thinks that the pressure is not suitable, charge/vent can be
done under the guidance of the supplier;
2. The working temperature and maximum working pressure are indicated on the label of
pressure tank body. It is strictly prohibited to use beyond this range;
3. The working medium of pressure tank is generally a mixture of water or antifreeze;
4. The pressure tank should be inspected regularly for its pre filling pressure, and if the