www.linearcorp.com 14 e3 eMerge Installation Instructions
5.3 System Outputs
All systems have door lock relays and auxiliary output relays that may be activated in response
to reader activity, time schedules or input conditions. All relays are Form-C SPDT and provide
non-powered dry contacts rated for 2A. e number of available door lock relays and auxiliary
output relays will depend on the number of licensed doors.
Output Defaults
All outputs are assigned default features that can be con gured as needed. e following table
shows the default states for each of the outputs:
Table 5.2: Default Output States
Output Default State Default Response
Door Lock Outputs Not Energized, Single Pulse
3 second unlock time in response to corresponding reader
activity (Reader 1 activates door 1 lock relay)
Aux Outputs Not Energized, Single Pulse No default response. Must be configured via programming.
Wiring Requirements
e cable must be the proper gauge for the current load and should not be routed in parallel
with other wiring especially high voltage or AC wiring. Refer to the Table 5.3 for wiring
recommendations:
Table 5.3: Recommended Wiring Requirements
Total Amps Voltage (AC or DC)
Wiring Gauges and Distance
14 16 18 20 22
.5 A
12V 1500 ft 1000 ft 600 ft 375 ft 225 ft
24V 2000 ft 1200 ft 750 ft 450 ft 300 ft
1.00 A
12V 800 ft 500 ft 300 ft 200 ft 100 ft
24V 1000 ft 600 ft 400 ft 200 ft 150 ft
2.00 A
12V 400 ft 240 ft 150 ft 90 ft 60 ft
24V 480 ft 300 ft 180 ft 120 ft 70 ft