www.linearcorp.com 5 e3 eMerge Installation Instructions
3.0 Installing the Control Panel
3.1 Mounting the Compact Enclosure
e housing is designed to accommodate the necessary wiring connections for most installations.
e compact enclosure is optimized to run wires under the back panel and thru the knockouts
shown in Figure 3.1 and Figure 3.2. e enclosure should be mounted vertically on a wall, in a
secure location within normal temperature and humidity levels.
Installing the Panel
1. Run all necessary wires to the panel location.
2. Remove the enclosure’s cover by removing the two screws in the front of the housing.
3. Level the enclosure on a sturdy wall. Mark the mounting holes with a pencil.
4. Partially insert screws into the top two mounting holes and hang the enclosure on the screws.
5. Pull all wires through the knock-out holes in the enclosure. Label each wire according to its use.
6. Recheck for level, insert the two lower screws, and tighten all four mounting screws.
Enclosure
Knockouts
Cover Screw
Cover Screw
Enclosure Knockouts
Mounting Hole
Cover
Tam per
EARTH
GROUND
& READER
SHIELD
LEAD
Wire Tie Down
Loops
Figure 3.1. Compact Enclosure
Note: The compact
enclosure will not
accommodate a backup
battery. If using a backup
battery, a separate
housing must be installed
or use PoE supply with
suitable UPS backup.
Note: The plastic
housing is not listed for
installations that require
UL 294.
Note: Tie down loops are
located in the enclosure
and used to provide
strain relief for fi eld
connections.
Note: This device
complies with Part
15 of the FCC Rules.
Operation is subject
to the following two
conditions: (1) this device
may not cause harmful
interference, and (2) this
device must accept any
interference received,
including interference
that may cause
undesired operation.
Note: Choose a centrally
located, secure, clean
and dry area near an
AC power source. Avoid
mounting the panel within
6 feet of any equipment
that generates electrical
interference.
Caution: This equipment
includes electronic
components that are
highly sensitive to
static electricity. Please
discharge by touching
an earth ground before
installing or handling this
equipment.