Installation, Configuration, and Programming
PN 15842:K 7/23/2002 35
4.11 Connecting Annunciator Key Switch and Phone Jack
After applying the
appropriate label, mount
key switch and/or phone
jack to the dress plate.
Plug the switch leads
from the Annunciator
Key Switch into the
keylock connector.
Note: Connector location
varies with annunciator
model; see Table 4-1:
Wire phone jack into
telephone circuit as
shown in Figure 4-17.
If annunciator is last jack
on telephone circuit, a
resistor is required on the
phone jack where shown.
Resistor rating varies depending on your system configuration:
If using a VCM-4 configured for telephone operation: 4.7K Ohm.
If using a FCM-1, a XP5-C, a XPC-8 or XPIQ circuit: 47K Ohm.
ACM-24AT,
ACM-48A
J2
ACM-16AT,
ACM-32A
J4
Table 4-1
-
+
Telephone
Circuit
Red
Red
Black
Black
acs-plusperiph.cdr, aksapj-wiring.cdr
Keylock
Connector
(see Table 4-1)
Resistor (for
last jack on
telephone
circuit)
Figure 4-17 Connecting Annunciator
Key Switch and Phone Jack
(ACM-16AT shown)
ABF-1, Back View
with Both Options Wired