AM2020/AFP1010 Systems
PN 15842:K 7/23/2002 61
P.4 Programming the AM2020/AFP1010 for Remote
Annunciation
Annunciator points must be programmed from the AM2020/AFP1010 before
the annunciators will function. The AM2020/AFP1010 employ the following
format for annunciator points:
Note: To program the annunciators into AM2020/AFP1010 memory, and to
map system points and software zones to annunciator points, refer to the
AM2020/AFP1010 Manual.
Note: When using the NCA to annunciate points on the AM2020/AFP1010 over
the network, enable state reporting in the AM2020/AFP1010 panel for control
module points and “NONA”/”NOA” module points; refer to the NCA Manual
for instructions.
A(xx) P(yy)
Annunciator address
In the range of 1-32,
as set on the
annunciator’s rotary
decimal switches.
Annunciator Points per Module
ACM-24AT,
Points 1-24
First
AEM-24AT,
Points 25-48
Second
AEM-24AT,
Points 49-64
Note: Points
65-72 are not
used
ACM-48A,
Points 1-48
AEM-48A
Points 49-64
Note: Points 65-96 are not used
ACM-16AT,
Points 1-16
First
AEM-16AT,
Points 17-32
Second
AEM-16AT,
Points 33-48
Third
AEM-16AT,
Points 49-64
ACM-32A,
Points 1-32
AEM-32A,
Points 33-64