EasyManua.ls Logo

Notifier ACS Series - System and Point Annunciation

Notifier ACS Series
100 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
AFP-300/AFP-400
PN 15842:K 7/23/2002 55
N.5 System and Point Annunciation
The control panel's annunciation points are divided into nine ACS Selection
Groups of 64 points. Table N-1, which follows, summarizes the ACS Selection
Groups and what an annunciator displays if a group is selected. The
AFP-300/AFP-400 installation manual provides a complete listing of the points
within the ACS Selection Groups and instructions on programming the panel for
addressable annunciators.
Note: Annunciators configured for point annunciation:
Do not respond to any status change that is not within its ACS Selection
Group. This includes system alarm or system trouble.
Do mask status changes for point number 1 of the start address selection.
Do not respond to System Reset, Acknowledge, or Alarm Silence.
Do not use the battery saving feature (100 mA battery load)
ACS
Selection
Group Annunciator Display
1 Control Panel Status and Zones 1-56
2 Zones 57-99, NAC Ckts 1-4 and 16 Special Zones
3 Intelligent Modules 101 to 164
4 Intelligent Modules 201-264 (AFP-400 only)
5 Intelligent Modules 165-196 and 265-296 (AFP-400 only)
6 Detectors 101 to 164 on SLC loop 1
7 Detectors 201-264 on SLC loop 2 (AFP-400 only)
8 Detectors 165-196 and 265-296 (AFP-400 only)
9 Panel Output Circuit Modules (64 points)
A Programmable annunciator group A; requires VeriFire™ 400
software to program
B Programmable annunciator group B; requires VeriFire™ 400
software to program
* or 0 Annunciator Not Installed At Address
Table N-1 Zone and Point Mapping With AFP-300/AFP-400