NFS-640 Systems
70 PN 15842:K 7/23/2002
Q.5 System and Point Annunciation
The control panel's annunciation points are divided into 13 ACS Selection
Groups of 64 points. Table O-1, which follows, summarizes the ACS Selection
Groups and what an annunciator displays if a group is selected. This fire alarm
control panel's Programming Manual provides a complete listing of the points
within the ACS Selection Groups and instructions on programming the panel for
addressable annunciators.
*Note: Defining Programmable Annunciator Groups requires VeriFire™ Tools.
Note: Annunciators configured for point annunciation:
Do not respond to any status change, including system alarm or system
trouble, that is not within its ACS Selection Group.
Do mask status changes for point number 1 of the start address selection.
Do not respond to System Reset, Acknowledge, or Alarm Silence.
Do not use the battery saving feature (100 mA battery load).
ACS Selection Group Annunciator Display
A 8 Systems points + Zones 1-56
B Zones 57-99, 8 F zones, 4 NAC
C Loop 1, Modules 1-64
D Loop 2, Modules 1-64
E Loop 1, Modules 65-128
F Loop 2, Modules 65-128
G Loop 1 - Modules 129-159, 2 unused points
Loop 2 - Modules 129-159, 2 unused points
H Loop 1, Detectors 1-64
I Loop 2, Detectors 1-64
J Loop 1, Detectors 65-128
K Loop 2, Detectors 65-128
L Loop 1 - Detectors 129-159, 2 unused points
Loop 2 - Detectors 129-159, 2 unused points
M Panel circuits 1-1 to 8-8 (64)
1 Programmable Annunciator Group #1 *
2 Programmable Annunciator Group #2 *
3 Programmable Annunciator Group #3 *
4 Programmable Annunciator Group #4 *
5 Programmable Annunciator Group #5 *
6 Programmable Annunciator Group #6 *
7 Programmable Annunciator Group #7 *
8 Programmable Annunciator Group #8 *
9 Programmable Annunciator Group #9 *
0 Programmable Annunciator Group #10 *
Table Q-1 ACS Selection Groups and the Annunciator
Display

Table of Contents

Other manuals for Notifier ACS Series