130 AFP-3030 Programming Manual — P/N DOC-01-032:A 26/06/2015
System Faults
AUXIN FAULT Generated when the auxiliary input is supervised (as determined in VeriFire™ Tools
programming) and no signal is coming from the input. Check wiring and source.
BACKUP AMP x FAIL The Backup Amp at address x has failed. Call Technical Services.
BACKUP AMP x HARDWARE FAIL The Backup Amp at address x has had a hardware failure. Call Technical Services.
BACKUP AMP x LIMIT The Audio Circuit of the Backup Amplifier at address x has been overloaded or shorted so the
Audio Signal has been attenuated. Check wiring and source and ensure that there are no
shorts.
BACKUP AMP x OVERCURRENT The Backup Amplifier at address x has overloaded and shut down. Check the total Load
calculations fir the DS-AMP and/or DS-BDA and ensure the total values do not exceed 120
watts.
BACKUP AMP x NOT INSTALLED The Backup Amplifier that is programmed at address x is not communicating with the DS-AMP.
Ensure the ribbon and power cables are properly attached to the DS-AMP and DS-BDA. If there
is no Backup Amplifier at that address, remove the Backup Amplifier from programming.
BACKUP AMP x TRIP The DS-BDA at DS-BUS address x (1-4) is drawing more current from the power supply than
expected and has been disabled. Refer to the DVC manual for additional troubleshooting.
BASIC WALK TEST A Basic Walk Test is in progress.
BATTERY The power supply’s battery voltage is too high or too low. Check the batteries for problems.
Replace batteries if necessary.
BUZZER OFF-LINE The piezo is disabled.
CHARGER FAIL The DAA’s battery charger is not functioning. Investigate and correct.
CORRUPT LOGIC EQUAT The database that houses the panel’s logic equations is corrupt. It must be re-downloaded, or
all programming must be cleared and re-entered.
DAA ADDRESS CONFLICT More than one DAA has the same address.
DAA DOWNLOAD IN PROGRESS The DVC is currently downloading to DAAs.
DAA NO ANSWER A DAA is not responding. Investigate and fix.
DAL DEVICE NO ANSWER The DAL device is no longer communicating with the fire panel. Check wiring and source
DAP PORT x FAILURE Digital Audio Port x (A or B) is not communicating due to a break in the connection, a short, or
faulty hardware. Locate and fix the break or short. If the problem is not a short or break, call
Technical Services.
DATABASE CORRUPTED The DVC programming database is corrupt. Re-create and/or re-download the database.
DATABASE INCOMPATIBLE The DVC programming database version is incompatible with DVC software.
DIGIN FAULT The DAA has determined that its DVC has stopped transmitting audio data to the Digital Audio
Loop (DAL), even though the loop is still functional. Update code, ensure all code on the DAL is
compatible. If the DVC still does not transmit digital audio data, call Technical Services.
DISPLAY COMM LOSS Communication with the keypad display has been lost. Check cable connection, investigate and
fix.
DISPLAY NODE LIMIT EXCEEDED The number of display nodes on the network has been exceeded. This fault will only be
displayed if at least one of the AFP-3030s on the network are in Network Display Mode and the
total number of display nodes has exceeded 25. Remove one or more display nodes to correct
this fault. (Display nodes include NCA-2, a Gateway node, or an AFP-3030 in Network Display
Mode.)
DOOR INTERLOCK FAULT A fault has occurred on the door interlock. Investigate and fix.
DRILL INITIATED Drill has been initiated locally.
DRILL RECEIVED Drill has been initiated remotely.
DSBUS x AC FAIL The DSBUS at address x has lost AC power. Check wiring and source.
DSBUS x COMMFAIL The DSBUS at address x is not communicating with the fire panel. Check wiring and source.
DSBUS x HIGH BATT The battery voltage for the DSBUS at address x has exceeded 28 V. If the batteries are shared,
ensure that only one power supply is charging the batteries. Remove the batteries and measure
the charging voltage from the supply to ensure it is not exceeding 27.6 V. Call Technical
Services.
DSBUS x LOW BATT The battery voltage for the DSBUS at address x has fallen below 20.4 V. Charge or replace
batteries.
DSBUS x SELF TEST FAIL A device on the DSBUS at address X has failed self test. Reboot the device. If this does not
repair it, update the software of the device. If the self test fail fault continues to be displayed, call
Technical Services.
EPROM ERROR The application and/or boot code is corrupt. Service required.
EXTERNAL RAM ERROR The external RAM test failed. Service required.
FLASH IMAGE ERROR The software is corrupt. Re-download the panel code software from VeriFire™ Tools. If the fault
does not clear, call Technical Services.
SYSTEM FAULTS
FAULT MESSAGE TYPE FAULT DESCRIPTION
Table G.2 System Fault Descriptions (2 of 4)

Table of Contents

Other manuals for Notifier AFP-3030

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier AFP-3030 and is the answer not in the manual?

Notifier AFP-3030 Specifications

General IconGeneral
BrandNotifier
ModelAFP-3030
CategoryControl Panel
LanguageEnglish

Related product manuals