NAC Coding
32 AFP-300/AFP-400 Programming PN 50259:C1 06/19/97
1$&&RGLQJ
1RWH 7KH FRQWURO SDQHO
DXWRPDWLFDOO\ VHQGV DQ DOHUW
VLJQDO WR DQ\ RI WKH IRXU
1RWLILFDWLRQ $SSOLDQFH &LUFX LWV
PDSSHG WR = DQG ) EXW Q RW
PDSSHG WR WKH DODUP VLJQDO
$IWHU PLQXWHV ZLWKRXW DQ
$FNQRZOHGJH RU 6LOHQFH WKH
DOHUW VLJQDO EHFRPHV VWHDG \
Control panel Notification Appliance Circuits with a CBE equation that includes F8 are
coded when activated by a fire alarm. These circuits are steady when activated
exclusively by an initiating device with a Hazard Alert Type Code. If using these NACs
for releasing or zone coding, do not include F8 in the CBE equation. Select the code
type on a system basis, through special zone F8. Table 34 contains coding selections:
Table 34 NAC Coding Selections
Code Signal
March Time (default) 120 PPM (Pulses Per Minute)
Two-Stage Alert signal – 20 PPM; General alarm signal: Steady on
California 10 sec. on, 5 sec. off, repeats
Temporal 0.5 on, 0.5 off, 0.5 on, 0.5 off, 0.5 on, 1.5 off, repeats