Autoprogram
3URJUDP &KDQJH
AFP-300/AFP-400 Programming PN 50259:C1 06/19/97 7
$XWRSURJUDPPLQJ
'HIDXOWV
Table 8 contains descriptions for the fields that display in the Autoprogram Default
screen for a detector:
Table 8 Autoprogram Default Fields
If a device exists in the control panel program, but is missing (no response from the
program), the control panel displays a screen similar to the following:
)LJXUH  $XWRSURJUDP 'HYLFH 'LVSOD\ 6FUHHQ
To delete the device from memory, press Enter. The next new device appears in the
display.
To keep the device in memory, press <Esc>. The control panel displays the
Program Change screen.
Field Description
SMOKE (PHOTO) Type code of the detector.
DETECTOR ADDR 101 Default custom label: 101 (1=loop 1; 01=address 01).
Z03
1RWH <RX FDQ FKDQJH
]RQHV DV ZHOO DV DGG IRXU
PRUH ]RQHV IRU HDFK
GHWHFWRU·V &%(
Default zone selection:
Zone 01 (Heat detectors)
Zone 02 (Ion detectors)
Zone 03 (Photo detectors)
Zone 04 (Laser detectors)
Zone 05 (Multisensor)
AL:8 (Photo default)
AL:6 (Ion default)
AL:6 (LPX default)
AL:5 (Multisensor
default)
The Alarm sensitivity level, with 9 the least sensitive Alarm level
and 1 the most sensitive Alarm level.
PA:8 (Photo default)
PA:6 (Ion default)
PA:6 (LPX default)
PA:5 (Multisensor
default)
Shows the Pre-Alarm level setting—a number between 0 and 9—
as follows:
0
– no Pre-Alarm.
1
– most sensitive Pre-Alarm level.
9
– least sensitive Pre-Alarm level.
**
*
The first asterisk (*) indicates the cooperative multi-detector
mode:
A combines the detector's alarm decision with the next address
above.
B combines the detector's alarm decision with the next address
below.
C combines the detector's alarm decision with the next address
above and the next address below.
*
– the second asterisk (*) indicates Alarm Verification (V=on,
*=off). Refer to “Interpreting a Detector Status Display or
Maintenance Report” on page 42 for more information on the
Alarm Verification feature.
352*50 602.( ,21 '(7(&725 $''5 
'(9,&( 127 $16:(5,1* '(/(7( )5 0(0 '
7\SH &RGH
7ZRGLJLW DGGUHVV
' GHWHFWRU RU 0 PRGXOH
6/& QXPEHU