System Defaults
8 AFP-300/AFP-400 Programming PN 50259:C1 06/19/97
6\VWHP'HIDXOWV
Autoprogram selects the following default system functions the first time you program
the control panel. System defaults do not appear on the display. Subsequent
Autoprogramming will not change previous editing of these functions.
1RWH )RU GHWDLOV RQ
SURJUDPPLQJ VSHFLDO ]RQHV
)) DQG 55 UHIHU WR
6SHFLDO =RQH &KDQJH RQ SDJH
)RU GHWDLOV RQ SURJUDPPLQJ
V\VWHP SDUDPHWHUV 5HIHU WR
´6\VWHP )XQFWLRQ
3URJUDPPLQJµ RQ SDJH
Table 9 contains a list of the default functions and values:
Table 9 System Defaults
Function Value
Zone 00 Custom label=General Alarm Zone
Zones 01 through 89 Custom label is blank
F0 Label=Presignal/PAS Delay; Delay=180; PAS=N
R0-R9 Label=Release Funct Release Control
ABORT=ULI; CROSS=N;
SOAK=0000; Delay=00
N/A
F5 and F6 Label=Time Function Time Control
Off=00:00; Days=SMTWTFSH
F7 Label=Holiday Funct; all days are 00/00
F8 Label=Code Type=March Time
F9 Label=Pre-Alarm Funct
Default=Alert
System Parameters (see Figure 28 on
page 18)
SIL INH=000
AUTO=000
VERIFY=30
USA TIME
TERM_SUPERV=NO
LocT
BLINK=Y
ST=4
ACS=N
Passwords Program Change=00000, Status Change=11111
All Systems Normal N/A
Custom Message 40 blanks