Programming 15088:J 10/22/99
3-43
Section Two
The Alter Status Menu
The Alter Status Mode is accessed by entering the following (level 1 password required):
C | X
After entering the Alter Status Mode, the display will show the Alter Status menu:
PRESS@1=DIS,2=CTL,3=DSEN,4=TIME,5=DIAG,6=WALK,7=GZON@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@@:
The Alter Status menu has six options, where:
1=DIS Disable - Disabling or enabling any individual addressable detector, module, or soft-
ware zone in the system.
2=CTL Control - Manually turning on and off a control module.
3=DSEN Detector Sensitivity - Altering the sensitivity of any of the addressable detectors in
the system.
4=TIME Time - Resetting the system time/date clock.
5=DIAG Diagnostics - Performing system diagnostics.
6=WALK Walk Test - Allows the programmer to select which Loop Interface Boards will partici-
pate in walk test and generates the walk test reports.
7=GZON Group Zone - Allows the programmer to select which zone (and its associated points)
to be disabled or enabled as a group.
The Alter Status Menu flow chart is located in Figure 2-1. Detailed information on the Alter Status options
follows.
NOTE
When an AM2020/AFP1010 with NOTIFIRENET is in walk test mode, a trouble condition will
appear for that AM2020/AFP1010 node at the INA and/or NRT.
www.PDF-Zoo.com

Table of Contents

Other manuals for Notifier AFP1010

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier AFP1010 and is the answer not in the manual?

Notifier AFP1010 Specifications

General IconGeneral
BrandNotifier
ModelAFP1010
CategoryFire Alarms
LanguageEnglish

Related product manuals