1-97
Installation 15088: J 10/22/99
Section 6.4 NFPA 72 Proprietary Supervising Station Fire Alarm Systems
Fire Alarm, Security Alarm, and Trouble Signal Transmission
All LIBs are power-limited. If the wiring connected to the LIB-200 leaves the building it must be in conduit. It can
not exceed 1000 meters (1093 yards), must not cross any power lines, and must not be in the vicinity of any high
voltage. These outdoor wiring restrictions do not apply to the LIB-200A or the LIB-400. Refer to Section 4.2 of
this manual and the Device Compatibility Document listed in the Related Documentation Chart of this manual for
information on surge suppressors approved for use with this FACP. Refer to Figures 6.4-1 and 6.4-2. Table 6.4-
1 is a minimal configuration for a NIB-96 with base SLC address=01 and may be used when programing the
NIB-96. For further information, refer to the NIB-96 Network Interface Board Manual.
Table 6.4-1 NIB-96 (Minimal Configuration)