Installation 15088:J 10/22/99
Table 3.2-1 AM2020/AFP1010 System Current Draw Calculations (2 of 2)
C
ATEGORY
COLUMN
A
P
RIMARY
,
N
ON
-F
IRE
A
LARM
C
URRENT
(
AMPS
)
(MPS-24A
OR
MPS-24E
OUTPUT
CURRENT REQUIRED WHEN OPERATING FROM
PRIMARY POWER
COLUMN
B
P
RIMARY
,
F
IRE
A
LARM
C
URRENT
(
AMPS
)
COLUMN
C
S
ECONDARY
,
N
ON
-F
IRE
A
LARM
C
URRENT
(
AMPS
)
Q
TY
X
[
CURRENT DRAW
]= T
OTAL
Q
TY
X
[
CURRENT DRAW
]= T
OTAL
Q
TY
X
[
CURRENT DRAW
]= T
OTAL
XP5 Series Transponders
XP5-M
XP5-C Relay
XP5-C NAC/telephone
[ ]
[ ]
[ ]
x[0.001651]=
x[0.000840]=
x[0.001481]=
[ ]
[ ]
[ ]
x[0.003000]=
x[0.000840]=
x[0.001481]=
[ ]
[ ]
[ ]
x[0.001651]=
x[0.000840]=
x[0.001481]=
Miscellaneous
CCM-1
A77-716B
RA-400Z(when on)
NIB-96
MBT-1
UZC-256
UDACT
[ ]
[ ]
[ ]
[ ]
n/a
[ ]
[ ]
x[0.107]=
x[0.020]=
x[0.006]=
x[0.022]=
n/a
x[0.035]=
x[0.100]=
[ ]
[ ]
[ ]
[ ]
[ ]
[ ]
[ ]
x[0.107]=
x[0.020]=
x[0.006]=
x[0.022]=
x[0.017]=
x[0.090]=
x[0.100]=
[ ]
[ ]
[ ]
[ ]
n/a
[ ]
[ ]
x[0.107]=
x[0.020]=
x[0.006]=
x[0.022]=
n/a
x[0.035]=
x[0.100]=
Notification Appliances
1
NOT APPLICABLE
[ ]
[ ]
x[ ]=
x[ ]=
NOT APPLICABLE
Other devices drawing power from
MPS-24A terminals TB3-3 and TB3-4
[ ]
[ ]
x[ ]=
x[ ]=
[ ]
[ ]
x[ ]=
x[ ]=
[ ]
[ ]
x[ ]=
x[ ]=
S
UBTOTALS FROM THIS PAGE
P
RIMARY
,
NON
-
ALARM
SUBTOTAL
:
P
RIMARY
,
ALARM
SUBTOTAL
:
S
ECONDARY
,
NON-FIRE
ALARM SUBTOTOTAL
:
S
UBTOTALS FROM PREVIOUS PAGE
P
RIMARY
,
NON
-
ALARM
SUBTOTAL
:
P
RIMARY
,
ALARM
SUBTOTAL
:
S
ECONDARY
,
NON-FIRE
ALARM SUBTOTOTAL
:
S
UM SUBTOTALS FROM EACH PAGE FOR
TOTALS
P
RIMARY
,
NON
-
ALARM
TOTAL
:
CANNOT
EXCEED
3.0
A
P
RIMARY
,
ALARM
TOTAL
:
CANNOT
EXCEED
6.0
A
S
ECONDARY
,
NON-FIRE
ALARM TOTAL
:
PLACE THIS TOTAL
IN TABLE 3.2-3 TO
DETERMINE A.H.
REQUIREMENT
1
I
NCLUDE ONLY THOSE DEVICES TO BE POWERED BY THE MAIN POWER SUPPLY
,
NOT AN AUXILIARY SUPPLY SUCH AS THE
AVPS-24
OR
APS-6R.
S
EE MANUFACTURER
'
S INSTRUCTIONS FOR APPLICABLE POWER DRAWS
.
www.PDF-Zoo.com

Table of Contents

Other manuals for Notifier AFP1010

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier AFP1010 and is the answer not in the manual?

Notifier AFP1010 Specifications

General IconGeneral
BrandNotifier
ModelAFP1010
CategoryFire Alarms
LanguageEnglish

Related product manuals