Section 2 Installation
PN 50702:B2 4/14/03 13
Wiring the APS-6R
This section contains instructions for wiring the APS-6R as follows:
Typical field wiring from an APS-6R to a control panel and
optional devices.
Wiring multiple APS-6R power supplies.
Field Wiring an APS-6R
J1 and J2 can be used in place of TB2 when the APS-6R is powering
internal modules (such as an ICM/ICE or XP6-C) with compatible
connectors.
Output Circuit 3 (J9) can be used as a source of power for the XPIQ
Audio Transponder only.
Note: When using the J9 connector do not use the J2 connector. This
will satisfy the 0.25 (6.35mm) requirement for separation between
power-limited and nonpower-limited circuits.
Primary and Secondary Power Connections - See appendix for your
specific system information.
CAUTION: When finished wiring AC connections, install
the press-fit terminal block cover over TB1 AC
connections.
CAUTION: To maintain proper supervision, APS-6Rs
used to power Panel Circuits, such as the ICM/ICE, must
be connected to the same batteries as the main power
supply. Failure to do so may result in improper operation.
!
www.PDF-Zoo.com
firealarmresources.com

Other manuals for Notifier APS-6R

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier APS-6R and is the answer not in the manual?

Notifier APS-6R Specifications

General IconGeneral
BrandNotifier
ModelAPS-6R
CategoryPower Supply
LanguageEnglish

Related product manuals