42 PN 15037:D2 9/9/02
• EIA-485 circuit rated 5.5 VDC max., 60 mA max.
• Each LCD-80 must have R-120 resistors installed across the in
and out terminals as shown in Figure 3-2.
• Set SW2 on the AFP-200 to the “Term” position (left-hand
position).
• Set SW4 and 5 on the LCD-80 to the “Term” position: SW1-7
“On”.
• The LCD-80s require connection of operating power! Connect
24 V power to the onresettable power connections on the panel,
or other appropriate power source as defined in Section 2.4
“Power Connections”.