52 NFS2-3030/E Installation Manual — P/N 52544:N1 07/18/2014
Applications Releasing Applications
4.5.9 Security Annunciation
A1P1
Mode: Monitor
Source: ZLc
A1P2
Mode: Monitor
Source: ZLe
A1P3
Mode: Monitor
Source: LXXMYY
A1P4
Mode: Monitor
Source: LXXMYY
Additional doors can be
monitored, up to the number of
available annunciator points.
4.6 Releasing Applications
4.6.1 Overview
This control panel can be used for non-hazardous agent release or preaction/deluge control
applications via the SLC loop. In a properly configured system with compatible, listed actuating
and initiating devices, this control panel complies with the following NFPA standards for
installation in accordance with the acceptable standard:
Refer to installation documents for the individual SLC loop device for voltage and maximum
current requirements.
4.6.2 Programming
The control panel supports up to ten releasing software zones. You can map these zones to activate
control modules. Program control module FCM-1 or FCM-1-REL for the appropriate Type Code
according to the chart below:
For more information, refer to the NFS2-3030 Programming Manual.
acm-24atface.cdr
Figure 4.10 Sample Annunciator Display
System Status
(red is armed)
System Alarm
(red is alarm)
Entry/Exit Door 1 Status
(red is unsecured)
Entry/Exit Door 2 Status
(red is unsecured)
Standard Covers
NFPA 13 Sprinkler Systems
NFPA 15 Water Spray Systems
NFPA 16 Foam-Water Deluge and Foam-water Spray Systems
NFPA 17 Dry Chemical Extinguishing Systems
NFPA 17A Wet Chemical Extinguishing Systems
NFPA 2001 Clean Agent Fire Extinguishing Systems
Table 4.1 NFPA Standards for Releasing Applications
Type Code: RELEASE CKT
For use in UL applications
Do not use REL-47K
Cannot use power-limited wiring
Supervised for open circuit only
Supervised for power loss
Type Code: REL CKT ULC
For use in UL or ULC applications
Requires REL-47K at solenoid
Power-limited wiring
Supervised for open circuit and shorts
Supervised for power loss

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier NFS2-3030/E and is the answer not in the manual?

Notifier NFS2-3030/E Specifications

General IconGeneral
BrandNotifier
ModelNFS2-3030/E
CategoryControl Panel
LanguageEnglish

Related product manuals