NFS2-3030/E Installation Manual — P/N 52544:N1 07/18/2014 11
Section 2: System Overview
2.1 System Description
This manual describes the NFS2-3030, based on the CPU2-3030D (with display) and
CPU2-3030ND (without display). It differs from the NFS-3030 as follows:
• It has been modified to include more memory.
• The display contains more information – a “Controls Active” LED and an “Acknowledge”
button.
• There are no panel module circuits – panel circuit module functions are performed by Digital
Voice Command equipment and SLC devices.
2.1.1 Standard Features
• Connections to easily mount from one to ten Signaling Line Circuit (SLC) loops
• Network operation
• Uses Notifier’s VIEW® early warning fire detection and the FlashScan® or CLIP families of
detectors and modules
• Alarm, Trouble, Supervisory and Security relays
• Support for 32 annunciator addresses with either 64 or 96 points each (depending on the
capability of the annunciator)
• Supports Style 4, Style 6, Style 7 SLC loops
• Logic Equations
• Multi-line display
• Ability to activate local sounder or relay bases in alarm or pre-alarm
• Alarm verification pre-alarm indication (NYC)
• Supervisory duct and smoke detectors
• Supports Intelligent Sensing algorithms
• EIA-485 connections for wiring ACS annunciators (including LDM custom graphic
annunciators), TM-4 transmitter
• EIA-232 connection for printer
• Autoprogram feature for faster programming of new devices
• Easy connection to VeriFire® Tools programming utility
• The basic system power supply is addressable, charges sealed lead-acid batteries ranging in
capacity from 7 to 200 amp hours, and provides up to 5 amps of power for use by the CPU.
• Easy connection to auxiliary power supplies and battery chargers for custom design of very
large systems.
• Diagnostic LEDs and switches
• Ground fault detection
• Support for Remote Text Display (LCD-160)
• Support for Display and Control Center (DCC) functionality
• Mass Notification System compatible