EasyManua.ls Logo

NTI TFTN - Page 110

NTI TFTN
116 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation and Operation Manual TFTN 085-199
110
Error Code
Problem
Possible Remedy
Error
Type
150 Common flow
sensor overheat
System sensor reading >
210°F
Faulty wiring check the wiring to the System sensor for
water or corrosion
Auto
reset
Faulty sensor check for proper readings from the System
sensor (see Table 18-2).
1P1 1 Flow check failed
(Supply Temp Change
Fast)
Outlet T-rise >
12.6°F/sec
Normal operation In systems with high and low
temperature zones this message may be appear serval
times as zones turn off and on.
Warning
1P2 1 Flow check failed
(Sensor Delta T Too
High)
Delta-T > 63°F
Normal operation In systems with high and low
temperature zones this message may be appear serval
times as zones turn off and on.
Warning
1P3 1 Flow check failed
(Supply Temp Too High)
Inlet > Outlet temp by
18°F
Normal operation In systems with high and low
temperature zones this message may be appear serval
times as zones turn off and on.
Warning
1P4 Low Water
Pressure
Water pressure reading
< 7 psi
Low water pressure raise the water pressure to a
minimum of 12 psi
Warning
Faulty wiring ensure the wire harness is connected to
the water pressure sensor. Check for broken wires
Faulty sensor replace pressure sensor
203 DHW Sensor
DHW tank sensor
reading is invalid
Incorrect setting DHW Mode is set as Tank Sensor”, but
a tank sensor is not being used. Change DHW Mode
setting to Aquastat
Warning
Tank sensor not connected Connect IWH tank sensor to
DHW SWITCH/NTC
Faulty wiring check the wiring to the Tank sensor for
water or corrosion
Faulty sensor check for proper readings from the Tank
sensor (see Table 18-2).
209 Storage tank
overheat
Tank sensor temp >
175°F
Plumbing problem Boiler water is circulating through
the IWH coil during CH serving correct piping; see Boiler
System Piping section
Warning
Tank sensor improperly installed ensure the tank sensor
is fully inserted into the well of the tank in the proper
location.
Faulty wiring check the wiring to the Tank sensor for
water or corrosion
Faulty sensor check for proper readings from the Tank
sensor (see Table 18-2).
2P2 Anti-legionella
function not finished
Anti-legionella function
is not complete (to
reset, switch the power
to the boiler off/on)
Anti-legionella Function turned on if the anti-legionella
function is not wanted, then set Anti-Legionella Function
= Off (see DHW Setup)
Warning
Boiler setting to low set DHW Modulation Setpoint =
180°F or higher (see User Menu)
Tank sensor improperly installed ensure the tank sensor
is fully inserted into the well of the tank in the proper
location.
Faulty wiring check the wiring to the Tank sensor for
water or corrosion
Faulty sensor check for proper readings from the Tank
sensor (see Table 18-2).
Plumbing problem verify that boiler water is circulating
to the IWH coil; see Boiler System Plumbing section

Other manuals for NTI TFTN

Related product manuals