TFTN 085-199 Installation and Operation Manual
301 – Display error
Eeprom
Power problem /
defective PCB
1.Test for proper voltage and grounding.
2.Switch the boiler OFF and ON at the main electrical
power supply. If the problem happens again replace the
main PCB
302 – Communication
error GP - GIU
Wiring between display and PCB issue:
1. Test for proper voltage and grounding.
2. Switch the boiler OFF and ON at the main electrical
power supply. If the problem happens again replace
the main PCB
Power problem – Check the wire connection between the
PCB and the display for damage, corrosion or other
problems.
PCB internal error (to
reset, switch the power
to the boiler off/on)
Water pressure sensor wiring damaged or shorted:
1. Check the water pressure switch wiring for damage or
shorts
2. Test for proper voltage and grounding.
Power problem – test for proper voltage and grounding.
Faulty PCB – if the problem persists, replace the PCB
> 5 resets in 15 minutes
(to reset, switch the
power to the boiler
off/on)
Check error history (see Error section) and correct the
source of the respective fault codes.
PCB internal error (to
reset, switch the power
to the boiler off/on)
Power problem – test for proper voltage and grounding.
Faulty PCB – if the problem persists, replace the PCB
PCB internal error (to
reset, switch the power
to the boiler off/on)
Power problem – test for proper voltage and grounding.
Faulty PCB – if the problem persists, replace the PCB
PCB internal error (to
reset, switch the power
to the boiler off/on)
Power problem – test for proper voltage and grounding.
Faulty PCB – if the problem persists, replace the PCB
309 – flame detection
while burner is off
Damaged flame sensor or flame sensor wire – check flame
sensor and flame sensor wire for damage, replace flame
sensor
Water damage – check flame sensor and PCB for water
damage or corrosion
Flooded combustion chamber – If the condensate drain
was blocked and the chamber flooded, dry the chamber
and flame sensor
PCB internal fault – If the Flame sensor wire is good and
the flame sensor has been replaced, replace the PCB
3P9 – Sched.
Maintenance-Call for
Service
Months to next
maintenance time has
elapsed
Service the boiler and select RESET from the Setup ->
Diagnostics -> Service menu; see Diagnostics section.
411 – Room sensor
circuit open or short
circuit Zone 1
Room sensor circuit
open or short circuit
Zone 1
BUS wiring damaged – Inspect BUS wiring for bad
connections
Damaged PCB – If nothing is wired to the BUS
connections, replace the PCB.
412 – Room sensor
circuit open or short
circuit Zone 2
Room sensor circuit
open or short circuit
Zone 2
BUS wiring damaged – Inspect BUS wiring for bad
connections
Damaged PCB – If nothing is wired to the BUS
connections, replace the PCB.