EasyManua.ls Logo

NTI TFTN - Page 112

NTI TFTN
116 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation and Operation Manual TFTN 085-199
112
Error Code
Problem
Possible Remedy
Error
Type
412 Room sensor
circuit open or short
circuit Zone 3
Room sensor circuit
open or short circuit
Zone 3
BUS wiring damaged Inspect BUS wiring for bad
connections
Auto
Reset
Damaged PCB If nothing is wired to the BUS
connections, replace the PCB.
441 Follower Boiler
Missing from BUS
Follower Boiler Missing
from BUS
Single boiler configured as a Manager boiler if this is a
stand-alone boiler, set Boiler Address = Single Boiler, see
Cascade Setup section
Warning
Follower BUS wires disconnected Inspect BUS wiring for
damage or shorts, BUS wiring is polarity sensitive.
Follower boiler turned off ensure power is on for all
boilers in cascade
460 External safety
lock
Open circuit at AUX
LIMIT
External limit switch wired to AUX LIMIT input is open
check device. If an external limit switch is not being used,
place a jumper across AUX LIMIT.
NOTE: error type is Manual Reset if parameter 24.6.5 is
set to Safety lock not volatile
Auto
Reset
501 1 Ignition failed
(x3)
Boiler failed to sense
flame signal during
ignition (3x in a row)
Improper Gas pressure verify that the gas pressure
during an ignition attempt is within the range specified in
section 9.0 Gas Valve and Burner Setup.
Manual
Reset
Blocked air-intake remove front cover and inspect the
venturi and boiler air inlet silencer for debris.
Blocked exhaust inspect exhaust for proper slope to
boiler and possible restrictions or blockages
Blocked condensate drain inspect condensate drain, if
the drain was clogged water may have entered the gas
valve. If the valve was wet, it must be replaced.
Improper LP conversion check conversion instructions,
increase the gas flow by adjusting the input screw. **A
combustion test must be performed if the gas valve is
adjusted.
No spark inspect the igniter for cracks or warping
(electrode gap should be 3/16"-1/4"). With the gas supply
valved off and the igniter removed, observe the spark
during the trial for ignition it should spark for 3-5
seconds. If there is no spark check that the spark
transformer receives 120VAC during the ignition trial.
Improper combustion settings adjust the gas valve
Throttle Screw to increase the gas flow. Once the boiler
remains lit set combustion. See section 9.0 Gas Valve
and Burner Setup.
Warning: this process may only be performed by a
qualified technician with a combustion analyzer
Faulty flame sensor if the boiler lights well and has a
strong flame, replace the flame sensor, and inspect the
flame sensor harness for shorts or damage.
502 Flame detected
out of sequence
Flame detected before
the gas valve was
turned on
Faulty flame sensor check the flame sensor and wiring
for damage, water or other possible shorts to ground
(replace flame sensor)
Auto
Reset
Faulty PCB if problem persists, replace the PCB.
504 Flame lost ten
times during run
Flame signal lost during
run (10x in a row)
Improper Gas pressure verify that the gas pressure
during an ignition attempt is within the range specified in
section 9.0 Gas Valve and Burner Setup.
Manual
Reset

Other manuals for NTI TFTN

Related product manuals