EasyManuals Logo

nvent RAYCHEM Elexant 4010i User Manual

nvent RAYCHEM Elexant 4010i
101 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #30 background imageLoading...
Page #30 background image
nVent RAYCHEM Elexant 4010i/4020i User Manual
RAYCHEM-AR-H60624-40X0iOpsManual-EN-1905 nVent.com
|
30







shown is less than 500 mA then an actual ground fault condition may exist.
IMPORTANT: 
associated wiring with a periodic internal test. If the test detects a failure, the controller will disconnect

IMPORTANT: To minimize nuisance alarms, the controller will not report a leakage current of less than
10 mAmps
.
Ground-Fault Trip


setpoint.
Procedure: If trip action is desired when a GF condition is detected, adjust the GF Trip current to the

IMPORTANT:
Default: ENABLED



IMPORTANT: In order to safely implement a ground-fault trip function, all non-grounded power


Ground Fault Turns Ratio
The controller also allows the user to adjust the Ground Fault Turns Ratio for applications where a
control module is monitoring GF using an external step-up or step-down current transformer. The ratio is
multiplied with the actual ground fault current measured to display the adjusted reading to the user. See
Section 5.8.2.2 for more details.
3.2.2.3 Trace Voltage

unit is operating at voltages lesser/higher than the design. In addition, the controller also measures and
reports the power line frequency.

the controller and the EHT load to a max of 277Vac.
-

external step-down transformer.
Voltage Turns Ratio
The Voltage Turns Ratio adjusts voltage readings for applications where a control module is measuring
-

the Trace Voltage value reaching the unit. See Section 5.8.3.2 for more details.
3.2.2.4 Trace Resistance
Trace resistance is used to generate alarms when heater resistance levels have increased/decreased


Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the nvent RAYCHEM Elexant 4010i and is the answer not in the manual?

nvent RAYCHEM Elexant 4010i Specifications

General IconGeneral
Brandnvent
ModelRAYCHEM Elexant 4010i
CategoryController
LanguageEnglish

Related product manuals