EasyManua.ls Logo

Oldham iTrans 2

Oldham iTrans 2
106 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
33
signals are wired into the RS485A and RS485B terminals on the board. See
Figure 4-9.
Figure 4-9 Wiring Diagram for the ModBus Interface
Setting the ModBus Address on the
Located on the back of the electronics module is an 8-position DIP switch.
This switch bank is used to set the ModBus Slave Address for the
unit. The address can be set from 1 to 255. Use the DIP switches to set the
binary representation of the desired address. 1 is bit zero, and 8 is bit 7. ON
represents a 1, and OFF represents zero. Refer to Appendix B for hex-to-
decimal equivalents.
Figure 4-10 Switch Bank for Setting ModBus Slave Address

Table of Contents

Related product manuals