6 – Digital Modules  27 
 
 
 
 
 Swiches  
(On: 1; OFF: 0)
   
Switches  
(ON = 1; OFF = 0) 
 
Module 
address 
 
1  2  3  4  5   
M odule 
Address
 
1  2  3  4  5 
1  1 0 0 0 0   17  1  0 0 0 1 
2  0 1 0 0 0   18  0  1 0 0 1 
3  1 1 0 0 0   19  1  1 0 0 1 
4  0 0 1 0 0   20  0  0 1 0 1 
5  1 0 1 0 0   21  1  0 1 0 1 
6  0 1 1 0 0   22  0  1 1 0 1 
7  1 1 1 0 0   23  1  1 1 0 1 
8  0 0 0 1 0   24  0  0 0 1 1 
9  1 0 0 1 0   25  1  0 0 1 1 
10  0 1 0 1 0   26  0  1 0 1 1 
11  1 1 0 1 0   27  1  1 0 1 1 
12  0 0 1 1 0   28  0  0 1 1 1 
13  1 0 1 1 0   29  1  0  1     1  1 
14  0 1 1 1 0   30  0  1 1 1 1 
15  1 1 1 1 0   31  1  1 1 1 1 
16  0 0 0 0 1   32  0  0 0 0 0 
Table 5: Addressing table (address depends on switch positions). 
Remarks: 
 
■  The physical address of a module (1 to 32) must be identical to the address 
stated on the configuration program COM43 in the central unit. 
■  During module replacement, all the configuration switches of a new module 
must be positioned in the same configuration as those of the the previous 
module. 
■  The 6 switches (
FRAME FILLING/REMPLISS TRAME) and 7 (DELAY/TEMPORISATION) 
must be set to OFF (options unused). 
■    An analog-input module systematically takes 8 addresses.  
End of line Resistor 
 
Solely for the last module of each line, 
set switch no.8 (
EOL 
RESISTOR/RESISTANCE F.D.L.
) to ON or set 
the jumper of the analog input PCB to 
Closed. 
 
006 
Figure 16: End of line resistor switch in 
position “ON”.