PLATINUM
TM
Series User’s Guide
20
Complete Menu Structure
Level
2
Level
3
Level
4
Level
5
Level
6
Notes
oN.oF
ACtN
RVRS
Off when > SP1, on when < SP1
dRCt
Off when < SP1, on when > SP1
dEAd
____
Deadband value, default = 5
S.PNt
SP1
Either Setpoint can be used of on/off, default is SP1
SP2
Specifying SP2 allows two outputs to be set for heat/cool
ALM.1
Output is an Alarm using ALM.1 configuration
ALM.2
Output is an Alarm using ALM.2 configuration
RtRN
Rd1
____
Process value for oUt1
oUt1
____
Output value for Rd1
Rd2
____
Process value for oUt2
oUt2
____
Output value for Rd2
RE.oN
Activate during Ramp events
SE.oN
Activate during Soak events
CyCL
____
PWM pulse width in seconds
RNGE
0–10
Analog Output Range: 010 Volts
0–5
0–5 Volts
0–20
0–20 mA
4–20
4–20 mA
0–24
0–24 mA
oUt2
oUt2 is replaced by output type
oUt3
oUt3 is replaced by output type
PId.S
ACtN
RVRS
Increase to SP1 (i.e., heating)
dRCt
Decrease to SP1 (i.e., cooling)
A.to
____
Set timeout time for autotune
AUto
StRt
Initiates autotune after StRt confirmation
GAIN
_P_
____
Manual Proportional Band setting
_I_
____
Manual Integral Factor setting
_d_
____
Manual Derivative Factor setting
%Lo
____
Low clamping limit for Pulse, Analog Outputs
%HI
____
High clamping limit for Pulse, Analog Outputs
AdPt
ENbL
Enable fuzzy logic adaptive tuning
dSbL
Disable fuzzy logic adaptive tuning
RM.SP
oFF
Use SP1, not remote Setpoint
oN
4–20
Remote analog Input sets SP1; range: 4–20 mA
Note: This submenu is the same for all RM.SP ranges.
RS.Lo
____
Min Setpoint for scaled range
IN.Lo
____
Input value for RS.Lo
RS.HI
____
Max Setpoint for scaled range