Most important specifications of the CMS 156:
Output voltages
3-phase AC (L-N) 3 x 0 to 250 V
1-phase AC (L-L) 1 x 0 to 500 V
DC (L-N) 3 x 0 to
± 250 V
Voltage outputs power
3-phase AC (L-N) 3 x 75 VA at 75 to 250 V
1-phase AC (L-N) 1 x 150 VA at 75 to 250 V
1-phase AC (L-L) 1 x 150 VA at 150 to 500 V
DC (L-N) 1 x 212 W at
± 150 to ± 250 V
Output currents
3-phase AC 3 x 0 to 25 A
DC 1 x 0 to
±25 A
Current outputs power
3-phase AC (L-N) 3 x 70 VA at 7.5 A
1-phase AC (L-L)1 1 x 140 VA at 7.5 A
DC (L-N) 1 x 140 W at
±10.5 A
Weight 14.9 kg (32.8 lbs)
Dimensions without handle
W x H x D 450 x 145 x 390 mm (17.7"
× 5.7" × 15.4")
Additional information about the CMS 156 can be found in the CMS 156
manual.
1
Single-phase model: two current phases in series.