6 - 9
6 DriveProgramming Commands
DriveProgramming User’s Manual (I622-E1)
6-3 Command List
6
Parameter Control Commands
Command Argument 1 Argument 2 Argument 3 Argument 4 Argument 5 Description
ChgParam
<parameter>
: =
<variable/
constant>
Replaces the content
of <parameter> with
<variable/constant>.
MonParam <variable> : =
<parameter>
Assigns the content of
<parameter> to
<variable>.
Inverter Control Commands
Command Argument 1 Argument 2 Argument 3 Argument 4 Argument 5 Description
FW : = 1
Operates the inverter
in the forward direction.
RV : = 1
Operates the inverter
in the reverse direction.
stop Decelerates the
inverter to a stop.
Note: This command
acts as a reset when the
inverter is in a trip state.
trip
<variable/
constant>
Issues a user trip
according to <variable/
constant>.
SET-Freq : =
<variable/
constant>
Assigns <variable/con-
stant> (× 0.01 Hz) to
the inverter frequency
reference variable.
ACCEL : =
<variable/
constant>
Assigns <variable/con-
stant> (× 10 ms) to the
inverter acceleration
time variable.
DECEL : =
<variable/
constant>
Assigns <variable/con-
stant> (× 10 ms) to the
inverter deceleration
time variable.

Table of Contents

Other manuals for Omron 3G3RX2-A2 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron 3G3RX2-A2 Series and is the answer not in the manual?

Omron 3G3RX2-A2 Series Specifications

General IconGeneral
BrandOmron
Model3G3RX2-A2 Series
CategoryInverter
LanguageEnglish

Related product manuals