8 Errors and Remedies
8 - 2
DriveProgramming User’s Manual (I622-E1)
8-1 Troubleshooting
This section describes the program operation at the time of error occurrence, the error codes that are
specific to the DriveProgramming, and the remedies for them.
Basically, even if the inverter detects a trip during the DriveProgramming operation, the operation is
continued. However, if any of E043 to E045 trips related to the DriveProgramming is detected, the oper-
ation is stopped. Or, with the “on trip goto” command, the program can jump to other process after a trip
occurred.
When the DriveProgramming program is stopped, the status before the program stop is
retained for output terminals controlled by the DriveProgramming.
For this reason, configure the system so that the stop of the DriveProgramming program in the
inverter can be detected by the DriveProgramming start signal and the alarm (trip) signal, and
the inverter's peripheral devices can be stopped safely.
8-1-1 DriveProgramming Operation on Error
With/without
“on trip goto”
Error status
User trip
E050 to E059
DriveProgramming
related trip E043 to E045
Other trips
Without Operation is continued. Program is stopped. Operation is continued.
With After the “on trip goto”
command is executed, the
program jumps to the
specified label and the
operation is continued.
Program is stopped. After the “on trip goto”
command is executed, the
program jumps to the
specified label and the
operation is continued.