Safety Precautions
Caution
(for installation and connection)
Carry the unit consider
ing its weight and balance, and place it on a
stable and robust base.
Dropping or toppling the unit may cause injury.
The approximate weight of the unit is 12.5 kg (BA75T/BA100T), 13 kg (BA100R).
If you drop the unit, stop using it and have it inspected and repaired.
For repair, contact us.
Keep plastic package bags out of reach of children.
Children may suffocate if they place their heads into plastic bags.
Make sure to connect the unit’s AC input to a commercial power source
with rated input
voltage (100 VAC,110VAC,115VAC,120VAC) and 50/60 Hz
frequency.
Connecting to a commercial power source with a different rated input voltage or
frequency may result in a fire.
The unit may fail.
When an abnormality (unusual sound or smell) occurs, t
urn OFF the
unit’s “Power” switch
to stop the output, and stop the supply of
commercial power. The socket-
outlet shall be installed near the
equipment and shall be easily accessible.
When performing maintenance on the connected devices, follow the above
instructions to ensure safety.
Do not connect devices such as dryers, some solenoid valves, etc.,
which have a half-wave rectifier that allows only half-cycle AC power to
flow through.
Overcurrent may damage the UPS.
When installing the input cable, make sure to perform the connection as
specified.
When connecting a cable to the terminal block, use a cable that complies with the
input current specification of the UPS.
Failure to do so may result in electric shock
or ground fault.
Provide secure grounding.
Connect the terminal to a commercial power source and ground it. A failure or leak
that occurs when the unit is not properly grounded may result in electric shock.
Do not disassemble, repair, or modify the unit.
Doing so may cause an electric shock or a fire.
Do not install the unit in other than specified orientations.
Dropping or toppling the unit may cause injury.
If you install the unit in an orientation other than specified, the unit cannot be
protected from a battery fluid leakage.
Do not use the unit where the maximum temperature exceeds 40°C.
The battery deteriorates rapidly.
Doing so may cause a failure or malfunction of the unit.