3 Check and start operation
3-1 The name and function for the operation and display
3-1-3 Switch
Sign of
the
Label Name Description
F
Power switch ON: Press the “Power” switch of the UPS. The power output from
the UPS begins.
OFF: Press the “Power” switch of the UPS in ON state, then the
power output from the UPS stops.
Additional Information:
・
If the AC input is connected to the commercial power source,
then the battery will be charged regardless of the “Power” switch.
Stop the beeper by pressing for 0.5 seconds or longer
3-1-4 Setting Switch
After changing the “Setting” switch, follow the procedure described below.
After changing the “Setting” switch, turn off the AC input, wait until the status indicator is
completely OFF, and then turn on the AC input.
Use a fine-pointed tool such as a small screwdriver to maneuver the switch’s lever.
1
Setting for beeper sound
in the event of power
Beeper sounds
Beeper does not
sound
2
Auto startup setting after
recovery from power
Auto startup is
performed
Auto startup is not
performed
3
Setting for whether or not
to perform test once
Test is performed
Test is not
performed
4
Auto startup mode setting
Logic of Remote on/off
signal
Short-circuit, Stop Open-circuit, Stop
7
8
Synchronous /
asynchronous
operation
setting
Bit 7 Bit 8 Operation Mode
OFF OFF
Commercial synchronous
operation (ECO mode disabled)
OFF ON
Commercial synchronous
operation (ECO mode enabled)
Asynchronous operation
(50 Hz output)
ON ON
Asynchronous operation
Setting switch function list
BA75T/BA100T/BA100R
35
3