154
Remote Terminals Section 5-1
The following diagram shows the terminal arrangement and wiring for the
SRT@-ID08.
Note The V terminals (terminal numbers 11 and 16) are all connected internally, as
are the G terminals (terminal numbers 3 and 8). When I/O power is supplied
to terminals 11 and 3, power can be supplied to sensors from terminals 16
and 8.
When the power supply exceeds 1.0 A, provide an external power supply to
the I/O power supply instead of providing the supply from the terminals.
The following diagram shows the terminal arrangement and wiring for the
SRT@-ID08-1.
Note The V terminals (terminal numbers 11 and 16) are all connected internally, as
are the G terminals (terminal numbers 3 and 8). When I/O power is supplied
to terminals 11 and 3, power can be supplied to sensors from terminals 16
and 8.
When the power supply exceeds 1.0 A, provide an external power supply to
the I/O power supply instead of providing the supply from the terminals.
CompoBus/S 24 V DC
Brown
Black
Blue
Brown
Blue
Brown
Black
Blue
CompoBus/S
communications
CompoBus/S
communications
power supply
I/O power supply
NPN output 3-wired
sensor (photoelec-
tric or proximity
sensor)
2-wired sensor
(limit switch)
NPN output 3-wired
sensor (photoelec-
tric or proximity
sensor)
PNP output 3-wired
sensor (photoelec-
tric or proximity
sensor)
2-wired sensor
(limit switch)
Brown
Black
Blue
Brown
Blue
CompoBus/S
communications
CompoBus/S
communications
power supply
I/O power supply
CompoBus/S 24 V DC