Loading...
229
Connector Terminals Section 5-2
Note 1. The node number of the 32-point Slave must be set to an even number. If
an odd number is input, the odd number less one will be set in the Slave.
2. The possible range of node numbers varies with the type of Master and
settings in the Master. Refer to 2-1 Communications Specifications for de-
tails.
Communications Mode Settings
The following communications modes are set with pin 3 of the DIP switch.
Note Make sure that the communications mode of the Slave is the same as that of
the Master Unit. If the communications modes are not the same, normal com-
munications with the Master Unit will not be possible. The operating status of
the Slave can be verified with LED indicators. Refer to 6-5-1 Indicators.
Internal Circuits
SRT2-ID32ML
The following diagram shows the internal circuits for the SRT2-ID32ML.
Node number Setting (Hex) Node number Setting (Hex)
0088
1199
2210A
3311B
4412C
5513D
6614E
7715F
Pin 3 Communications
mode
Communica-
tions distance
Communica-
tions baud rate
Communica-
tions cycle
time
OFF High-speed Com-
munications Mode
100 m max. 750 kbps 0.5 or 0.8 ms
ON Long-distance Com-
munications Mode
500 m max. 93.75 kbps 4.0 or 6.0 ms
Internal circuitry
Photocoupler
Photocoupler