323
Analog Output Terminals Section 5-8
The following diagram shows the terminal block for the SRT2-DA02.
Wiring Wire the connector terminals of the Analog Output Terminal as shown below
according to voltage output or current output.
Output Range and
Conversion Data
The digital values that are input are converted to analog data according to the
output range.
1 to 5 V
Values 0000 to 1770 Hex (0 to 6000) correspond to voltages between 1 and
5 V. The output range is 0.8 to 5.2 V.
NC
NC NC 0– 1–
BD
H
BS
+
BD
L
BS
NC V0+ I0+ V1+ I1+
NC NC
Voltage Output Current Output
CompoBus/S
communications
CompoBus/S
communications
power supply
(including
internal circuit
power supply)
External
device
External
device
BS
+
BS
+
BD
H
BD
L
BD HBD L
I+
+
V+ I+
V+
+
Voltage
Hexadecimal
(decimal)
conversion data
FED4
(–300)
189C
(6300)
1770
(6000)
0000 (0)
1 V
0 V
0.8 V
5.2 V
5 V
8000
7FFF