324
Analog Output Terminals Section 5-8
0 to 5 V
Values 0000 to 1770 Hex (0 to 6000) correspond to voltages between 0 and
5 V. The output range is –0.25 to 5.25 V.
0 to 10 V
Values 0000 to 1770 Hex (0 to 6000) correspond to voltages between 0 and
10 V. The output range is –0.5 to 10.5 V.
–10 to 10 V
Values F448 to 0BB8 Hex (–3000 to 3000) correspond to voltages between –
10 and 10 V. The output range is –11 to 11 V.
Negative voltages are specified as 2s complement (16 bits).
Voltage
Hexadecimal
(decimal)
conversion data
FED4
(–300)
189C
6300
1770
6000
0000 (0)
0 V
–0.25 V
5.25 V
5 V
8000
7FFF
Voltage
Hexadecimal
(decimal)
conversion data
FED4
(–300)
189C
(
6300
)
1770
(
6000
)
0000 (0)
0 V
–0.5 V
10.5 V
10 V
8000
7FFF
Voltage
Hexadecimal
(decimal)
conversion data
F31C
(–3300)
F448
(–3000)
0CE4
(3300)
0BB8
(3000)
0000 (0)
0 V
11 V
10 V
–10 V
–11 V
8000
7FFF

Table of Contents