23
Wiring Section 3-2
PWM(891) Output
Specifications (OUT4 and
OUT5)
Note The CJ1W-CPU21 supports only OUT4. OUT5 cannot be used.
3-2 Wiring
3-2-1 Connector Pin Allocations
Item Specifications
Max. switching capacity 300 mA, 4.75 to 26.4 V DC
Max. output frequency 1 kHz
PWM(891) output accuracy ON duty: +5%/0% for a 1-kHz pulse output
Output waveform
Pin layout
Code Name Input
signal type
Pin
No.
*1 Code Name Input
signal type
Pin
No.
*1
IN0 General-purpose input 0
Interrupt input 0
Quick-response input 0
Origin search 0
(Origin Input Signal)
24 V DC 1 A1 IN1 General-purpose input 0
Interrupt input 0
Quick-response input 0
Origin search 0
(Origin Proximity Input
Signal)
24 V DC 2 B1
LD+ 3 A2 LD+ 4 B2
0 V/LD
5A3 0 V/LD 6B3
IN2 General-purpose input 2
Interrupt input 2
Quick-response input 2
High-speed counter 1
(Phase-Z/Reset input)
Origin search 1
(Origin Input Signal)
24 V DC 7 A4 IN3 General-purpose input 3
Interrupt input 3
Quick-response input 3
High-speed counter 0
(Phase-Z/Reset input)
Origin search 1
(Origin Proximity Input
Signal)
24 V DC 8 B4
LD+ 9 A5 LD+ 10 B5
0 V/LD
11 A6 0 V/LD 12 B6
IN4 General-purpose input 4
Origin search 0
(Positioning Completed
Signal)
24 V DC 13 A7 IN5 General-purpose input 5
Origin search 1
(Positioning Completed
Signal)
24 V DC 14 B7
LD+ 15 A8 LD+ 16 B8
0 V/LD
17 A9 0 V/LD 18 B9
IN6 General-purpose input 6
High-speed counter 1
(Phase-A, Increment, or
Count input)
24 V DC 19 A10 IN7 General-purpose input 7
High-speed counter 1
(Phase-B, Decrement, or
Direction input)
24 V DC 20 B10
LD+ 21 A11 LD+ 22 B11
0 V/LD
23 A12 0 V/LD 24 B12
IN8 General-purpose input 8
High-speed counter 0
(Phase-A, Increment, or
Count input)
24 V DC 25 A13 IN9 General-purpose input 9
High-speed counter 0
(Phase-B, Decrement, or
Direction input)
24 V DC 26 B13
LD+ 27 A14 LD+ 28 B14
0 V/LD
29 A15 0 V/LD 30 B15
OUT0 General-purpose output 0
In CW/CCW mode:
Pulse output 0 (CW)
In Pulse + Direction
mode:
Pulse output 0 (pulse)
--- 31 A16 OUT1 General-purpose output 1
In CW/CCW mode:
Pulse output 0 (CCW)
In Pulse + Direction
mode:
Pulse output 1 (pulse)
--- 32 B16
OUT2 General-purpose output 2
In CW/CCW mode:
Pulse output 1 (CW)
In Pulse + Direction
mode:
Pulse output 0 (direction)
--- 33 A17 OUT3 General-purpose output 3
In CW/CCW mode:
Pulse output 1 (CCW)
In Pulse + Direction
mode:
Pulse output 1 (direction)
--- 34 B17
OUT4 General-purpose output 4
Origin search 0
(Error Counter Reset Out-
put)
PWM(891) output 0
--- 35 A18 OUT5 General-purpose output 5
Origin search 1
(Error Counter Reset Out-
put)
PWM(891) output 1
*2
--- 36 B18
--- Power supply input (+V) for
the output
--- 37 A19 --- Not used --- 38 B19
--- Output COM --- 39 A20 --- Output COM --- 40 B20
ON
OFF
T
t
ON
50
%
ON duty =
t
ON
T
X 100%
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
39
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40