3 Data Exchange with the CPU Unit
3-36
CJ-series DeviceNet Units Operation Manual for NJ-series CPU Unit(W497)
*_Mstr1FixAlocErr BOOL R Master
Fixed Allo-
cation Area
Setting
Failed
<Operation specifications>
TRUE:
Indicates that an error occurred in one of
the following operations:
*_Sw1MstrFixAloc1Cmd (Master Fixed
Allocation Setting 1 Switch)
*_Sw1MstrFixAloc2Cmd (Master Fixed
Allocation Setting 2 Switch)
*_Sw1MstrFixAloc3Cmd (Master Fixed
Allocation Setting 3 Switch)
Once this bit changes to TRUE, it will
remain TRUE until the operation is suc-
cessfully completed.
FALSE:
Indicates that the error did not occur. The
bit changes to FALSE when the operation
is successfully completed.
Default: FALSE
*_Mstr1SListRegErr BOOL R Scan List
Register/
Clear Failed
<Operation specifications>
TRUE:
Indicates that an error occurred in one of
the following operations:
*_Sw1SListEnblCmd (Scan List Enable
Switch)
*_Sw1SListClrCmd (Scan List Clear
Switch)
Once this bit changes to TRUE, it will
remain TRUE until the operation is suc-
cessfully completed.
FALSE:
Indicates that the error did not occur. The
bit changes to FALSE when the operation
is successfully completed.
Default: FALSE
Name of device variable for
CJ-series Unit
Type R/W Area Function

Table of Contents