4-3
4 Remote I/O Master Communications
CJ-series DeviceNet Units Operation Manual for NJ-series CPU Unit(W497)
4-1 Master Remote I/O Communications
4
4-1-1 Allocations
You can use *_Sw1MstrFixAloc1Cmd to *_Sw1MstrFixAloc3Cmd (Master Fixed Allocation Setting 1 to
3 Switch) to specify where a slave is allocated in the following fixed allocation areas 1 to 3. The output
(OUT) block and the input (IN) block are allocated to a certain area as shown below in the order of node
address.
To access the allocated area from the user program, a user-defined variable that specifies the AT spec-
ification of that area needs to be defined.
Words are allocated to slaves that start from address 0 in the output (OUT) and input (IN) blocks. Each
address is allocated at least one byte (rightmost).
More than one word is allocated for each slave (according to its node address) with more than16
I/O points.
The rightmost byte of the word is allocated to each slave that has 8 I/O points or less.
The following methods are used for user-set allocations:
Using the CX-Integrator
Using the device variable for CJ-series Unit (Master User-set Allocations Setup Table)
Fixed Allocations
User-set Allocations
Memory used for CJ-series Unit
NJ Series
User program
CIO 3200
CIO 3263
CIO 3200
CIO 3201
:
CIO 3262
CIO 3263
CIO 3300
CIO 3363
Address 0
Address 1
:
Address 62
Address 63
CIO 3300
CIO 3301
:
CIO 3362
CIO 3363
Address 0
Address 1
:
Address 62
Address 63
To SlavesFrom Slaves
CIO 3400
CIO 3463
CIO 3400
CIO 3401
:
CIO 3462
CIO 3463
CIO 3500
CIO 3563
Address 0
Address 1
:
Address 62
Address 63
CIO 3500
CIO 3501
:
CIO 3562
CIO 3563
Address 0
Address 1
:
Address 62
Address 63
To SlavesFrom Slaves
CIO 3600
CIO 3663
CIO 3600
CIO 3601
:
CIO 3662
CIO 3663
CIO 3700
CIO 3763
Address 0
Address 1
:
Address 62
Address 63
CIO 3700
CIO 3701
:
CIO 3762
CIO 3763
Address 0
Address 1
:
Address 62
Address 63
To SlavesFrom Slaves
Output
(OUT)
block 1
Input
(IN)
block 1
User-defined
variable
User-defined
variable
User-defined
variable
Specify using master fixed
allocation setting switches 1-3.
Input
(IN)
block 2
Input
(IN)
block 3
Output
(OUT)
block 2
Output
(OUT)
block 3
Master Fixed Allocation
Setting 1 Switch
Master Fixed Allocation
Setting 2 Switch
Master Fixed Allocation
Setting 3 Switch