3-15
3 Data Exchange with the CPU Unit
CJ-series DeviceNet Units Operation Manual for NJ-series CPU Unit(W497)
3-2 Device Variables for CJ-series Unit (Software
Switches, Statuses)
3
3-2-1 Software Switches 1
*_Sw1MstrAlocCmd BOOL RW Master
User-set
Allocations
Switch
<Operation specifications>
FALSE→TRUE:
Reads setting data from
*_MstrAlocTblCfg[0] to
*_MstrAlocTblCfg[5] (Master User-set
Allocations Setup Table) and registers the
scan list. (The Unit automatically restarts.)
Once registered, the Unit will operate with
master user-set allocations until the scan
list is cleared, regardless of whether the
power is turned OFF and back ON again.
FALSE:
Returns to FALSE when the scan list is
registered and the Unit starts operating
with the scan list enabled.
Note
If there is a setting information error,
an error code will be stored in
*_MstrAlocTblCfgSta (Setting Results
of Master User-set Allocations Setup)
and *_Mstr1SListRegErr (Scan List
Register/Clear Failed) will change to
TRUE.
Default: FALSE
<Operation conditions>
• CPU Unit is operating in PROGRAM
mode.
• Master function is enabled.
Name of device variable for
CJ-series Unit
Type R/W Area Function