132
Yes
No
Check the voltage at
the IR 00002 and IR
00003 terminals.
Check operation by using a
dummy input signal to turn the
input ON and OFF.
No
Replace the CPU
Unit or Expansion
I/O Unit.
Are the terminal
screws loose?
Operation
O.K.?
Wire correctly.
Is input wiring
correct?
Tighten the terminal
screws
Check input devices
LS1 and LS2.
Return to “start.”
Are the IR 00002
and IR 00003 input indi-
cators operating
normally?
Operation
O.K.?
Replace the CPU
Unit or Expansion
I/O Unit.
Operation
O.K.?
Yes
Yes
Yes
Yes
NoNo
No
No
No
No
No
Check the voltage at
the IR 00002 and IR
00003 terminals.
A
From
previous
page
Yes
Troubleshooting Flowcharts
Section 5-6

Table of Contents

Other manuals for Omron CPM1A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron CPM1A and is the answer not in the manual?

Omron CPM1A Specifications

General IconGeneral
ModelCPM1A
TypeCompact PLC
Communication PortsRS-232C (optional)
Instruction SetBasic and advanced instructions
Operating Temperature0 to 55°C
Storage Temperature-20 to 75°C
Humidity10% to 90% RH (non-condensing)
Power Supply24 VDC or 100-240 VAC
ExpansionExpansion I/O units available
Timers128
Counters256 counters
I/O Points10, 20, 30, or 40 points (depending on model)

Related product manuals