10-7SectionResults Storage Area Response Codes
188
Response
code
Probable remedyDescriptionUNIX error
message
0053 ETIMEDOUT Connection timed out (TCP timed
out)
Check the remote host and communications
path.
0063 ESELABORT Used for internal Ethernet Unit pro-
cessing
Close the local socket and try reopening it.
0066 (None) Internal memory cannot be
allocated for processing; the
service cannot be provided.
Traffic is too high at the Ethernet Unit. Correct
the user application to reduce traffic at the
Ethernet Unit.
0080 (None) Timed out for passive TCP open re-
quest
Either the remote node is not executing an ac-
tive TCP open or there is a block on the net-
work.
0081 (None) Closed by close command during
socket servicing
No action is necessarily called for.
0082 (None) Connection with remote node not
achieved for passive TCP open re-
quest
The remote IP address and TCP port number
settings differ from those of the remote socket
(active side).