11-3SectionCommand/Response Reference
203
11-3-12 UDP CLOSE REQUEST
Requests processing to close a socket.
Command Block
0427
Command
code
UDP
socket
number
Results storage area
Response Block
0427
Command
code
Response
code
Results Storage Format
Response
code
Parameters
The UDP socket number to be closed specified as 2 bytes between 1 and 8.
The area in which the results of the command execution are stored. The first byte
specifies the memory area and data type (variable type). The 2nd to 4th bytes
specify the beginning address of the results storage area. Refer to page 192 for
details about the variable types and addresses that can be specified.
Response Codes
Response code Description
0000 Normal
0105 Local IP address setting error
0302 CPU Unit error; execution not possible.
1001 Command too large
1002 Command too small
1100 UDP socket number is out of range.
1101 The variable type for the results storage area is out of range.
1103 Non-zero bit address specified for the results storage area.
2210 Specified socket is not open.
2211 High traffic at Unit; cannot execute service.
Results Storage Area Response Codes
Response code Description
0000 Normal
UDP Socket Number
(Command)
Results Storage Area
(Command)