193
Adjustment Level Section 5-4
This parameter enables/disables writing of parameters to the Digital Con-
trollers from the host (personal computer) using communications.
This parameter is not displayed if communications write enable/disable is
set for execution using an event input assignment 1 to 4.
ON: Writing enabled
OFF: Writing disabled
Default: OFF
Related Parameters
MB command logic switching (advanced function setting level): Page 252
Communications unit No., Communications baud rate, Communications data
length, Communications parity, Communications stop bits (communications
setting level): Page 281
This parameter enables or disables infrared communications between the
host (personal computer) and the Digital Controller.
Set this parameter to ON only when connecting to a Setup Tool, and leave
it set to OFF during normal operation.
ON: Infrared communications enabled.
OFF: Infrared communications disabled.
Default: OFF
This parameter is used to select the SP mode.
In Local SP Mode, the local SP set in bank is used as the target value in
the control operation. In Remote SP Mode, the remote SP set via an
external signal (e.g., 4 to 20 mA) is used as the target value in the control
operation.
cmwt Communications Writing
Communications must be supported.
The Event Input Assignments 1 to 4
parameters must not be set to
enable communications writing.
Function
Setting
See
See
irdr Infrared Communications Use
Infrared communications must be
supported.
Function
Setting
spmd SP Mode
The ST parameter must be set to
OFF.
The Remote SP Enable parameter
must be set to ON.
The Event Input Assignment 1 to 4
parameters must not be set to switch
to SP mode.
Setting range Default
RSP: Remote SP, LSP: Local SP LSP
Function
Setting