Advanced Function Setting Level Section 5-10
This parameter sets the time constant for the input digital filter. The follow-
ing diagram shows the effect on data after passing through the digital fil-
ter:
This parameter adds a display at the beginning of the operation level for the
process value (PV). If there is no need to display the set point, use this to dis-
play only the present temperature.
Set to ON to display, and OFF to not display.
inf Input Digital Filter
Setting range Unit Default
0.0 to 999.9 Second 0.0
Function
0.63 A
A
PV before passing through filter
PV after passing through filter
(Time
constant)
In
p
ut di
g
ital filter
Time
Setting
pvad Additional PV Display
Setting range Default
on: Displayed, off: Not displayed off
Function
Setting