Connecting to Ethernet Section 5-1
IMPORTANT When an NE1A-series Controller that supports EtherNet/IP is started with the
IP address switch pressed, the Controller will be given a fixed starting IP
address of 192.168.250.1. When starting the Controller in this mode, set the
IP address before executing any other operations.
5-1-2 TCP/IP Settings
Using the Network Configurator to Make the Settings
1,2,3... 1. Select Programs - OMRON Network Configurator for DeviceNet Safety
- Network Configurator from the Windows Start Menu. The Network Con-
figurator will start.
2. Connect the Network Configurator online. (Select Option - Select - Inter-
face to set the interface, and then select Network - Connect.)
3. Select EtherNet/IP in the Network Configuration Window. (Example: Click
the EtherNet/IP_1 Tab.)
4. Select Tools - TCP/IP Settings. The Setup TCP/IP Configuration Dialog
Box will be displayed. The default settings are given in the dialog box
shown below.
5. In the Target IP Address, set the present IP address for the applicable
NE1A-series Controller.