Installation Section 3-1
3-1-2 Mounting to the Control Panel
Use the NE1A-series Controller in an enclosure with IP54 protection or
higher according to IEC/EN 60529.
Use DIN Track (TH35-7.5/TH35-15 according to IEC 60715) to mount the
NE1A-series Controller in the control panel. Mount the Controller to the
DIN Track using PFP-M End Plates (not included with the NE1A-series
Controller) to prevent it from falling off the DIN Track because of vibration.
Provide sufficient space around the NE1A-series Controller, at least 5 mm
at the sides and at least 50 mm at the top and bottom, for ventilation and
wiring.
Note The NE1A-series Controller can be mounted only to DIN Track. Do not screw
the Controller to the control panel.
50 mm min.
50 mm min.
5 mm min.
5 mm min.
35-mm DIN Trac
k
End Plate
Model: PFP-M
Wiring duct
Wiring duct