Command Reference: Function Blocks Section 8-5
Error Handling and Error Resetting
Timing Chart
8-5-11 Routing
Diagram
General Description
The Routing function block routes one input signal to a maximum of eight out-
put signals. It is used to output a signal to more than one output tag.
Optional Output Settings
The number of outputs can be increased on the In/Out Setting Tab Page in the
function block property dialog box.
Error Behavior for error detection Resetting the error
condition Outputs 1
and 2
Fault
Present
Error output condition
EDM feedback
time error
OFF (safety
state)
ON EDM Error output: ON Remove the cause of
the error and turn ON
the safety input.
Monitored
input
Output1
EDM
Feedback
EDM Error
Fault
Present
Output2
Idle
to RUN
TEDM TEDM TEDM TEDM TEDM
Default Maximum Number of Outputs
Parameter Setting range Default setting
Number of outputs 1 to 8 1