35
Specifications Section 2-2
2-2-2 DeviceNet Communications Specifications
2-2-3 EtherNet/IP Communications Specifications (Controllers That
Support EtherNet/IP)
Item Specifications
Communications
protocol
Conforms to DeviceNet.
Connection method The multidrop and T-branch connections can be combined (for main line and branch lines).
Baud rate 500 kbits/s, 250 kbits/s, 125 kbits/s
Communications
medium
Special cable with 5 lines (2 communications lines, 2 power lines, 1 shield line)
Communications
distance
Baud rate Maximum network length Branch length Total length
500 kbits/s 100 m max. (100 m max.) 6 m max. 39 m max.
250 kbits/s 250 m max. (100 m max.) 6 m max. 78 m max.
125 kbits/s 500 m max. (100 m max.) 6 m max. 156 m max.
The numbers in parentheses are the lengths when Thin Cable is used.
Communications power
supply
11 to 25 VDC
Connected nodes 63 nodes max.
Safety I/O
communications
(Pre-Ver. 1.0 Controllers)
Safety Master Function:
Maximum number of connections: 16
Maximum data size: 16 bytes input or 16 bytes output (per connector)
Connection type: Single-Cast, Multi-Cast
Safety Slave Function:
Maximum number of connections: 4
Maximum data size: 16 bytes input or 16 bytes output (per connector)
Connection type: Single-Cast, Multi-Cast
Safety I/O
communications
(Controllers with unit ver-
sion 1.0 or later)
(including Controllers
that support EtherNet/
IP)
Safety Master Function:
Maximum number of connections: 32
Maximum data size: 16 bytes input or 16 bytes output (per connector)
Connection type: Single-Cast, Multi-Cast
Safety Slave Function:
Maximum number of connections: 4
Maximum data size: 16 bytes input or 16 bytes output (per connector)
Connection type: Single-Cast, Multi-Cast
Standard I/O
communications
Standard Slave Function
Maximum number of connections: 2
Maximum data size: 16 bytes input and/or 16 bytes output (per connector)
Connection type: Poll, Bit-strobe, COS, Cyclic
Message communica-
tions
Maximum message length: 552 bytes
Item Specifications
Media access method CSMA/CD
Modulation method Baseband
Transmission path type Star topology
Baud rate 10Base-T: 10 Mbits/s
100Base-TX: 100 Mbits/s
Transmission medium Twisted-pair cable (shielded: STP): Category 5, 5e
Transmission distance 100 m (distance between hub and nodes)
Number of cascade connections There is no limit when a switching hub is used.